• The Site Sheet
  • Posts
  • ⚡ Code Corner:🔸 NEC Article 270 – Capacitors

⚡ Code Corner:🔸 NEC Article 270 – Capacitors

Sharpen your knowledge with a quick dive into the NEC.

📘 What NEC 270.3 says:

What it says:
270.3 Flammable Liquids. Capacitors containing more than 3 gal (11 L) of flammable liquid shall be installed in a vault or outdoor fenced enclosure, or in a manner acceptable to the authority having jurisdiction (AHJ) to minimize the risk of fire.

Why it matters:

  • Ampacity and OCPD ensure safe operation under normal and fault conditions.

  • Guarding protects unqualified individuals from accidental contact—especially around liquid-filled or high‑voltage systems.

  • Proper discharge prevents shock hazards from residual voltage.

💡 Pro Tip: If you're installing capacitors indoors and they contain more than 3 gallons of flammable dielectric fluid, you cannot rely on bollards, signage, or locked doors alone.
To comply with 270.3, the system must be placed inside a code-compliant vault or relocated outdoors in a fenced, locked enclosure that meets NEC Article 110, Part III.

🔧 Bonus Tip:
When planning capacitor installations, always confirm the fluid type and volume—many installers overlook this when submittals don't specify the dielectric's flash point or volume.

❓ Quick Code Quiz

Choose the correct answer:

❓ Question:
You're installing a 600 V-rated capacitor bank in a facility where unqualified personnel have occasional access. The capacitors contain more than 3 gallons (11 liters) of flammable liquid.

According to NEC Article 270, what is the correct installation requirement?

A) The capacitors must be installed in a standard NEMA 1 enclosure.
B) No enclosure is required as long as conductors are properly rated.
C) The capacitors must be installed in a vault or fenced outdoor enclosure.
D) The disconnecting means may be omitted if a circuit breaker is present upstream.

Answer below 👇

🧠 Think it through – Before you choose your answer, consider the risk profile here:

  • You're dealing with flammable liquid — more than 11 liters.

  • The space is not restricted to qualified personnel only.

  • What happens in a fault? Arcing + flammable fluid = fire or explosion hazard.

This is exactly the type of scenario where the NEC draws a hard line: if the quantity of flammable dielectric liquid exceeds 3 gallons, the installation must be physically protected, regardless of access frequency or enclosure type.

 Answer: C) Per NEC 270.3, capacitors containing more than 11 liters of flammable liquid must be installed in vaults or fenced outdoor enclosures to protect against fire hazards, especially in accessible areas.

📘 Reference:
NEC 2020 — Article 270.3

“Capacitors containing more than 3 gallons (11.4 L) of flammable liquid shall be installed in a vault in accordance with 450.41 or in an outdoor enclosure that is located at least 5 feet (1.5 m) from walls, buildings, or other enclosures and is protected against unauthorized access.”

This ensures safety from fire and explosion hazards due to large quantities of flammable dielectric fluid — especially in publicly accessible areas.