- The Site Sheet
- Posts
- ⚡ Code Corner: 🔸 NEC 314.28(A)(2) – Pull Box Sizing: Straight Pulls
⚡ Code Corner: 🔸 NEC 314.28(A)(2) – Pull Box Sizing: Straight Pulls
Sharpen your knowledge with a quick dive into the NEC.
📘 What NEC 314.28(A)(2) says:
What it says:
When conductors enter and exit a box in a straight line (same wall to opposite wall), the box must be at least 8 times the trade diameter of the largest conduit in the run.
Why it matters:
Undersized pull boxes make wire pulls brutal—and risky. NEC sizing ensures there's enough space for bending and pulling, reducing strain on conductors and minimizing insulation damage during installation.
💡 Pro Tip:
If you're running a 3" conduit straight through a pull box, the box must be at least 24 inches long in the direction of the pull. This is a minimum—larger is often better for future access.
❓ Quick Code Quiz: Chapter 3 – Pull and Junction Boxes
Choose the correct answer:
Question:
You’re installing a straight-through pull using 2" EMT. What’s the minimum length the pull box must be in the direction of the pull?
A) 12 inches
B) 16 inches
C) 8 inches
D) 10 inches
Answer below 👇
🧠 Think it through:
Multiply the largest trade size (2") by 8—because it's a straight pull, not an angle or U-pull.
✅ Answer: B) 16 inches
📘 Reference:
NEC 2023 – Article 314.28(A)(2): Boxes and Conduit Bodies – Sizing Pull and Junction Boxes
“Where splices or straight pulls are made, the length of the box shall not be less than 8 times the trade size of the largest raceway.”