- ⚡ Code Corner:🔸 NEC 300.4(B)(1) – Protection from Physical Damage
⚡ Code Corner:🔸 NEC 300.4(B)(1) – Protection from Physical Damage
Sharpen your knowledge with a quick dive into the NEC.
📘 What NEC 300.4(B)(1) Says:
When nonmetallic-sheathed cable, MC cable, or other wiring methods pass through holes in wood framing members (like studs) and those holes are less than 1 ¼ inches from the edge of the wood, the cables must be protected from nails, screws, or anything else that might puncture them.
❓ Quick Code Quiz:
True or False?
❓ Question:
You’re running NM cable through a 2x4 stud wall. The hole you drilled is 1 inch from the edge of the stud. What must you do to comply with NEC 300.4(B)(1)?
A) Nothing — the cable is fine as is
B) Cover the hole with electrical tape
C) Install a steel plate at least 1/16" thick to protect the cable
D) Move the hole closer to the edge so it’s easier to staple
Answer below 👇
✅ Answer:
C) Install a steel plate at least 1/16" thick to protect the cable