• The Site Sheet
  • Posts
  • ⚡ Code Corner:🔸 NEC 250.96(B) – Bonding for Over 250 Volts

⚡ Code Corner:🔸 NEC 250.96(B) – Bonding for Over 250 Volts

Sharpen your knowledge with a quick dive into the NEC.

📘 What NEC 250.96(B) says:

What it says:
If you're working on systems over 250 volts to ground, and your metallic raceways or enclosures are relying on concentric or eccentric knockouts, then you must provide a bonding jumper or other listed bonding method to ensure a continuous low-impedance path for fault current.

Why it matters:
If a short circuit happens (say, a hot wire touches the metal box or conduit), the only way the breaker trips fast enough to prevent a fire is if there's a solid, low-resistance path for that fault current to return. Without proper bonding, the fault current might be weak — causing arcing, overheating, or even fire.

💡 Pro Tip: When working on 277/480V systems, always assume that concentric or eccentric knockouts do not meet bonding requirementseven if the fitting seems tight.

✅ Use a bonding bushing with a grounding lug, and land a jumper to the ground bar or grounding electrode conductor.
✅ For services and transformer-fed panels, bonding is even more critical—inspectors are watching.

🧠 Remember: If fault current can’t flow freely, it won’t trip the breaker. That’s when things burn.

❓ Quick Code Quiz: Chapter 6: Pools & Bonding

Choose the correct answer:

❓ Question:
You’re running a 480V feeder in metallic conduit between two equipment enclosures. According to NEC 250.96(B), when is bonding required?

A) Only if it’s a wet location
B) Always, for circuits over 250 volts
C) Only when using PVC
D) Never, metallic conduit is self-bonded

Answer below 👇

🧠 Think it through – Metal raceways are not automatically grounded just by being connected—especially when eccentric or concentric knockouts are used. The NEC requires a low-impedance path for fault current, and bonding jumpers or bushings provide that reliability.

 Answer: B) Always, for circuits over 250 volts

📘 Reference:
NEC 2023 – 250.96(B) – Bonding of Enclosures for Over 250 Volts to Ground

NEC 250.96(B) – Bonding of Equipment for Over 250 Volts
“Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and other metal non–current-carrying parts that are to serve as a bonding path shall be bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them.”

  • Feeder and branch circuits over 250V to ground

  • Metal raceways/enclosures that may use concentric/eccentric knockouts

  • Conditions where a secure electrical bond is critical for fault clearing