- The Site Sheet
- Posts
- ⚡ Code Corner:🔸 NEC 225.37 – Identification of Disconnecting Means
⚡ Code Corner:🔸 NEC 225.37 – Identification of Disconnecting Means
Sharpen your knowledge with a quick dive into the NEC.
📖 What NEC 225.37 says:
"Where a disconnecting means is required for a building or structure, it shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident."
👷 What It Means on the Job:
When you run a feeder to a separate building or structure, the disconnect (usually an outdoor panel or disconnect switch) must be:
Clearly labeled to show what it shuts off
Legible and permanent
Not just a Sharpie on a panel door!
🧰 Field Example:
You’re installing a 200A disconnect on the exterior wall of a detached shop. You must label it something like:
“Feeder Disconnect – Shop Building”
(Or more specific, depending on what’s inside)
If there’s more than one feeder to the same building? Each disconnect must be separately labeled — don’t just call both “Shop.”
🚩Common Mistakes:
Leaving it blank (“I’ll do it later…”)
Writing with a marker that fades in the sun
Using abbreviations no one understands (“W.B. SWD PNL” 😵)
✅ Pro Tip:
Use engraved placards or UV-stable labels with:
Panel name
Voltage
Building/structure served
Feeder # if there’s more than one
🔦 Why It Matters:
Saves time in emergencies
Helps inspectors
Complies with 225.37
Avoids red tags and costly rework
❓ Quick Code Quiz
Choose the correct answer:
Question:
You install a 200A disconnect for a feeder supplying a detached storage unit. Which of the following is required by NEC 225.37?
A) The disconnect must be locked
B) The disconnect must be painted red
C) The disconnect must be labeled to show which building it serves
D) The disconnect must be fire-rated
🧠 Think it through:
This Code section is all about identification, not physical protection or color. While locking or painting might be helpful, they aren’t required. The only mandatory step? Making sure anyone looking at the disconnect knows exactly what it controls.
✅ Answer:
C) The disconnect must be labeled to show which building it serves.
NEC 225.37 requires legible labeling of the disconnecting means so it clearly identifies what building or structure it controls. This helps prevent confusion during service, inspections, and emergencies — even when multiple feeders are involved.
📘 Reference:
NEC 225.37 – Identification of Disconnecting Means
"Where a disconnecting means is required for a building or structure, it shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident."
This avoids confusion during emergencies, service work, or inspections — and keeps your install compliant from day one.